ION 7500 / ION 7600 User’s Guide

Internal Modem Connections

Chapter 5 - Features and Applications

Page 135

The ModemGate Protocol

The ModemGate feature creates a communications connection between the
telephone network and an RS-485 serial network of devices. When you specify the
protocol for a meter’s COM port as M

ODEMGATE

, all data received by the meter’s

internal modem is automatically transferred to the serial network. ModemGate is
available on either COM1 and COM 2, but you cannot use the protocol on both
ports simultaneously.

ModemGate connections do not connect a workstation with ION Enterprise (or
other master device) to the gateway meter’s COM1 or COM 2 port, but rather the
gateway meter’s internal modem port (COM 3).

The example below illustrates how the ION Management Console’s Sites and
Devices windows appear:

Refer to the ION Meter as a ModemGate technical note for complete details on
configuring your meter for ModemGate.

Telephone

Network

Meter with an internal

modem on COM 3.

The serial network is

connected to COM1.

Workstation with

ION Enterprise

and modem

Each device on the RS-485 loop,

including the gateway meter’s internal

modem, must have a unique Unit ID.

All serial devices must operate at the

same baud rate as the gateway meter.

The Modem Site

The ION 7600 with
internal modem

The RS-485 device network

connected to the meter with

the internal modem.

The same RS-485 serial

protocol must be selected

for connections to multiple

devices along the same bus.