Using the Onboard Digital Outputs

ION 7500 / ION 7600 User’s Guide

Page 142

Chapter 5 - Features and Applications

Configure the settings of the controlling module to match your requirements. The
settings in these modules are as follows:

1

See “Calibration Pulsing Relay DO4,” below.

Ensure that the module’s Port setup register matches the meter’s output you want
to control. If the port you want to use does not appear in the Port setup register’s
list, that port is in use by another module. Edit the port setup register of the module
using that port and set it to

NOT

USED

– the port will then be available to other

modules.

Calibration Pulsing Relay DO4

Solid-state relay DO4 is factory configured for calibration pulsing and requires no
further setup. The Calibration Pulser module labeled kWh Pulser –D4 controls this
port. By default, the module is linked to the kW del+rec output of the Arithmetic
module labeled “del, rec” (in the Demand Framework). (This Arithmetic module is
linked to the MU Power Meter module’s MU kW tot output.) The port will output
a pulse for every 1.8 Wh accumulated (in

NORMAL

or

TEST

mode). This is the same

pulsing rate as the middle LED on the front panel of the meter.

ION Module

Setup Registers

Available Settings

Creation Default

Description

Digital Output

Port

Not Used

Port DO1

Port DO2

Port DO3
Port DO4

1

Port R1

Port R2

Port R3

kWh Pulse –LED

Alarm LED

Not Used

The output hardware channel

Pulse Width

0 to 2000000

0

Pulse Width, in seconds

(0 for continuous pulse)

Polarity

Inverting or Non-Inverting

Non-Inverting

Inverted or non-inverted output

EvLog Mode

Log on or Log off

Log off

Whether or not to log status changes in

the Event Log

Pulser

Port

As per Digital Output, above

Not Used

The output hardware channel

PulseWidth

0.020 to 2000000

1

Pulse width, in seconds

OutputMode

Pulse or KYZ

Pulse

Full pulse or KYZ (transition pulse)

Polarity

Inverting or Non-Inverting

Non-Inverting

Inverted or non-inverted output

Calibration

Pulser

Port

As per Digital Output, above

Not Used

The output hardware channel

Pulse Width

0.010 to 1.000

0.05

Pulse Width, in seconds

Kt

0.01 to 1000000000

1.8

Watts per pulse

Int Mode

Forward, Reverse, Absolute, or Net

Absolute

Integration modes that may be selected

OutputMode

Pulse or KYZ

Pulse

Full pulse or KYZ (transition pulse)

Advertising