ION 7500 / ION 7600 User’s Guide

Power Quality Configuration

Chapter 3 - Default Meter Functionality

Page 59

The following setup registers are available in the Calibration Pulser module:

1

Refer to the Calibration Pulser module description in the online

ION Programmer’s Reference

for more

details.

Power Quality Configuration

Power quality configuration is provided by a number of modules, depending on
your meter type: the Sag/Swell module, the Transient module, and numerous
EN50160 frameworks, some of which include the Mains Signalling Evaluation
modules.

Sag/Swell Module Settings

The Sag/Swell module monitors voltage waveforms for sags and swells (i.e. ITI
(CBEMA) Type 2 and Type 3 disturbances); it then reports each disturbance’s
magnitude and duration. The Sag/Swell module can also detect sub-disturbances
during a Sag/Swell event. Settings are as follows:

1

The primary power system voltage is sometimes different than the PT Primary setup register value (i.e.
when the PT Primary is used to indicate winding ratio rather than primary voltage).

Setup Register

Function

Default

Pulse Width

This numeric bounded register specifies the width, in seconds, of the pulses sent to the hardware

channel. The Calibration Pulser module maintains a minimum duty cycle of 50% on the output pulse

train.

0.05

Kt

The numeric bounded register defines how much energy the module accumulates before a pulse is

sent to the hardware channel. An industry standard for energy pulsing is 1.8, or one pulse per 1.8

energy-hours.

1.80

Int Mode

Specifies the modes of integration that may be selected.

1

Absolute

OutputMode

This register specifies whether the output is a complete pulse (Pulse) or a change of state transition

(KYZ).

Pulse

Port

This register specifies which hardware port the output appears on. Only those hardware channels that

are still available appear when you access this setting.

Not Used

Setup Register

Function

Default

Swell Lim

This is the magnitude above which a voltage deviation is

considered a swell.

106

Sag Lim

This is the magnitude below which a voltage deviation is considered

a sag.

88

Change Crit

This is the amount a voltage signal must change during a

disturbance to be considered a new sub-disturbance.

10

Nom Volts

This is the nominal power system voltage (used for all Power

Quality functions).

0

1

EvPriority

The priority assigned to Sag/Swell and Transient module events

(0 to 255, 255 is highest).

200