Mechanical relay outputs – Multi-Tech Systems 7500 User Manual

Page 170

Advertising
background image

I/O Specifications

ION 7500 / ION 7600 User’s Guide

Page 170

Chapter 6 - Hardware Reference

Mechanical Relay Outputs

Specifications for the three Form C relays (R1, R2 and R3) are as follows:

1

Consult the device’s operating instructions or manufacturer for assistance if required.

Specification

Standard I/0

Rated Voltage

250 VAC / 30 VDC

Rated Load @ Rated Voltage

10 A resistive 7.5 A (AC) / 5 A (DC) Inductive (p.f. = 0.4)

Max. Voltage

380 VAC, 125 VDC, Installation category III (Distribution),

Pollution degree 2

Max Load @ Max Voltage

0.2A (DC) / 3A (AC)

Max. Switching Load

2,500 VA resistive

1,875 VA inductive (p.f. = 0.4)

Isolation

5,000 VAC for 1 minute

Lifetime

no load: 10,000,000 operations

rated voltage and load: 100,000 operations

Turn-On Time

8.3 ms Max (60 Hz)

Turn-Off Time

AC: 8.3 ms Max (60 Hz)

DC: 5 ms Max

Update Time

½ cycle or 1-second

Connector Type

Ring or spade

Wire Type

Use the appropriate gauge wire for the amount of current
that could be drawn by the connected device

1

Additional External Excitation (Optional)

Internal Excitation

Rear View of Meter

Standard I/O

mechanical relays

Advertising
This manual is related to the following products: