ION 7500 / ION 7600 User’s Guide

Power Frequency

Power Quality: ION Meters and EN50160 Technical Note

Page 303

Power Frequency Default Measurements

* This data is recorded once a week by Data Recorder module 17.

Optionally, the data below can be recorded every 10 minutes by Data Recorder 32.

Register Label

Source Module Type

Description

Freq N*

Signal Limit Evaluation

number of valid intervals (voltage on all phases within +/- 15% of nominal)

Freq N invld*

number of invalid intervals

Freq N1*

number of valid intervals in which the freq deviates from the nominal by more than +/-1%

Freq N2*

num of valid intervals in which the freq deviates from the nominal by more than +4% or -6%

PO Freq N

Store

Freq N of the previous Observation Period

PO Freq N1

Freq N1 of the previous Observation Period

PO Freq N2

Freq N2 of the previous Observation Period

Freq mean-ep

Sliding Window Demand

average Frequency over 10s (used for display purposes)

Freq mn-op

Minimum

minimum mean Frequency (Freq mean-ep) over 1week (used for display purposes)

Freq mx-op

Maximum

maximum mean Frequency (Freq mean-ep) over 1week (used for display purpose)

Freq N1/N

Arithmetic

N1/N ratio

Freq N2/N

N2/N ratio

PO Freq N1/N

N1/N ratio of the previous Observation Period

PO Freq N2/N

N2/N ratio of the previous Observation Period

Register Label

Description

PQ Freq mean

average Frequency over 10minutes

PQ Freq low

minimum Frequency over 10 minutes (HS measurement)

PQ Freq high

maximum Frequency over 10 minutes (HS measurement)