ION 7500 / ION 7600 User’s Guide

Basic Setup Menu

Chapter 2 - Using The Front Panel

Page 33

Basic Setup Menu

The Basic Setup menu contains values that typically do not need to be reconfigured
once the meter is put into service. The Basic Setup menu item provides access to the
following power monitoring system settings:

1

Polarities can be normal or inverted.

2

Applicable to meters ordered with the current probe input option.

All Basic Setup menu items are setup registers in the Power Meter module. See the
online ION Programmer’s Reference for details.

The Current Probe phase calibration registers are setup registers in the Factory
module that can be configured in a Telnet or HyperTerminal session. Up to three
separate groups of registers (Factory Default, User Defined 1, and User Defined 2) can
be set up for three different Current Probes. In the Basic Setup menu, the Probe Type
register is used to activate one of those register groups. Only the selected group is
used in the meter’s calculations.

Sub-Menu

Register

Default Description

PT/CT Setup

Volts Mode

4 Wire Wye

The power system’s configuration

PT Primary

120

The Potential Transformer’s primary winding voltage rating for VA, VB, and VC

PT Secondary

120

The Potential Transformer’s secondary winding voltage rating for VA, VB, and VC

CT Primary

5

The Current Transformer’s primary winding current rating for IA, IB, and IC

CT Secondary

5

The Current Transformer’s secondary winding current rating for IA, IB, and IC

V4 Setup

V4 Primary

120

The potential transformer’s primary winding rating on input V4

V4 Secondary

120

The potential transformer’s secondary winding rating on input V4

I4/I5 Setup

I4 Primary

5

The current transformer’s primary winding rating on input I4

I4 Secondary

5

The current transformer’s secondary winding rating on input I4

I5 Primary

5

The current transformer’s primary winding rating on input I5

I5 Secondary

5

The current transformer’s secondary winding rating on input I5

V Polarity

1

VA Polarity

Normal

The polarity of the potential transformer on VA

VB Polarity

Normal

The polarity of the potential transformer on VB

VC Polarity

Normal

The polarity of the potential transformer on VC

V4 Polarity

Normal

The polarity of the potential transformer on V4

I Polarity

1

IA Polarity

Normal

The polarity of the current transformer on IA

IB Polarity

Normal

The polarity of the current transformer on IB

IC Polarity

Normal

The polarity of the current transformer on IC

I4 Polarity

Normal

The polarity of the current transformer on I4

I5 Polarity

Normal

The polarity of the current transformer on I5

Current
Probe

2

Probe Type

Factory Default

Current Probe Input setting – selects phase angle correction method for I1, I2, I3