Diagnostics and event logging, Diagnostics module output registers, Event logging – Multi-Tech Systems 7500 User Manual

Page 355: Diagnostics module output registers event logging

Advertising
background image

ION 7500 / ION 7600 User’s Guide

Diagnostics and Event Logging

Time Synchronization & Timekeeping Technical Note

Page 355

Diagnostics and Event Logging

The meter’s Diagnostics module includes output registers that provide time
synchronization diagnostics. Events are logged by the meter’s Clock module,
Communications modules, and Diagnostics module in response to time
synchronization events.

Diagnostics Module Output Registers

Time Sync Source

This register is

ON

if the internal clock synchronizes with the line frequency or

GPS, and it is

OFF

if the internal clock synchronizes with its own internal crystal.

GPS Receiver Status

This register is

ON

if the GPS receiver is locked onto a time source and

OFF

if the

lock is lost. This information is received directly from the GPS receiver; the
register is

NOT

AVAILABLE

if the GPS time synchronization is not used.

Time Sync Count

This register indicates how many time synchronization signals have been
received. The value increases with each signal received.

Time Since Last Time Sync

This register displays the amount of time, in seconds, since the last time
synchronization signal was received.

Time Sync Diag (time sync diagnostics)

This register displays the difference, in microseconds, between the timestamp
in a synchronization signal and the time in the device’s clock when the signal is
received. The displayed value is a sliding window average over the last five
time synchronization signals received.

Time Sync Status

This register is

ON

if a time synchronization signal is acquired, and

OFF

if the

signal has been lost. The Diagnostics module calculates the average interval for
the last five signals received, considering the signal lost if no signals are
received in two times the average interval.

Event Logging

The following events appear in the Event Log:

Time sync acquired — generated when the first time sync signal is received
(Diagnostics module’s Time Sync Status register goes

ON

).

Time sync lost event — generated if no time sync signals are received in two
times the average interval of the last five signals (Diagnostics module’s Time
Sync Status register goes

OFF

).

GPS locked — generated when the GPS receiver locks onto a time source
(Diagnostics module’s GPS Status register goes

ON

).

Advertising
This manual is related to the following products: