Communications Setup

Chapter 3 - Default Meter Functionality

Page 51

Once basic setup is performed (i.e. the PT/CT and Volts Mode settings), the meter
operates properly. Typically there is no need to make further changes to the Power
Meter module’s setup registers.

Communications Setup

Communication settings are typically configured when the ION meter is initially
put into service. Each communications port on a meter is controlled by a single
Communications module. The modules’ setup registers define the parameters
used for each port, so parameters do vary according to the type of communications
channel selected (i.e. RS-232, RS-485, Modem, Infrared, Ethernet).

The Communications modules control the following channels:

A communications channel must be configured before you can use ION software
(i.e. Vista or Designer). Altering the settings of a channel that is in use causes a loss
of communications with the meter.

Module Name

Settings

Comm 1

Selectable RS-232 or RS-485 port on COM1

Comm 2

High-speed RS-485 port on COM2

Comm 3

IrDA optical (infrared) RS-485 port or optional internal modem on COM3

Ethernet

Optional 10Base-T or 10Base-FL Ethernet port

Communications Port

Setup Register

Function

Default

all Serial ports

Protocol

This sets the serial port’s communications protocol

ION

all Serial ports

Baud Rate

This sets the communications speed in bits/second

9600 bps

all Serial ports

RTS Delay

This sets the RTS Delay for the serial communications port

0.01s (10ms)

all Serial ports

Unit ID

This sets the meter’s Unit ID

(A unique Unit ID is required for each device, including all the

devices on a ModemGate or EtherGate serial loop.)

COM1: Unit ID is based
on the serial number.

1

COM2: 101

COM3: 102

COM1

and COM3

Mode or

Comm Mode

This sets the communications standard the hardware channel

employs.

COM1: RS-232 or RS-485

COM3: IRDA optical port or internal modem

COM1: RS-232

COM3: Modem

COM1 (RS-232) only

HshakeMode

Specifies the handshake mode the device is using when the

Comm Mode is set to RS-232

RTS with Delay

COM3 (internal modem)
only

2

Answer

Hours Rings

This specifies the number of rings during defined answer

hours. Valid entries for this register are 0-255 rings; an entry

of 0 rings will disable answering.

1

Non-Answer

Hours Rings

This specifies the number of rings during defined non-answer

hours

5