Description of KCTSTP and KCTRD Calibration Commands

ION 7500 / ION 7600 User’s Guide

Page 190

Current Probe Inputs Basic Setup Technical Note

KCTRD

Read all current probe setup registers

Description:
This command lists the content of all current probe setup registers. There are three
identical groups of registers: Factory Default (configured in the factory), User
Defined 1, User Defined 2 (both for user configuration).

Each group contains the following probe parameters:

Primary Nominal Current, Secondary Nominal Voltage, Probe Name Tag
(character string). Additionally, if the meter was ordered with factory calibrated
current probes, then the Factory Default register group contains probe phase
compensation coefficients.

For meters equipped with Current Probe Input Option, but not ordered with
factory calibrated current probes, all register groups should contain zero values,
except for Nominal Current and Voltage, which are set to 1.0 by default.

For meters NOT equipped with Current Probe Input Option, all register groups
should contain zero values, except for Nominal Current and Voltage, which are set
to 1.0 by default.

Arguments:
None