ION 7500 / ION 7600 User’s Guide

Data Logging Setup

Chapter 3 - Default Meter Functionality

Page 57

Sag/Swell and Transient Logging

The meter logs the following ION output register values:

EN50160 Compliance Logging (ION 7600 only)

By default, 22 Data Recorders are used for logging EN50160 compliance
parameters.

The ION 7600 logs EN50160 counter data for current and previous observation
periods. EN50160 events are also logged. EN50160 parameter data logging (from
seven “Prm” data recorders) is disabled by default. The EN50160 Parameter
Logging enable is accessible in the default Power Quality Vista diagram. For more
information about EN50160 data logging, refer to the technical note Power Quality:
ION Meters and EN50160.

Sag/Swell Log

DistDur

DistV2Engy

DistV1Engy

DistV3Engy

DistV1Min

DistV3Min

DistV2Min

DistNominal

DistV1Max

DistV3Max

DistV2Max

SwellLim

DistV1Avg

DistV3Avg

DistV2Avg

SagLim

Transient Log

TranV1Dur

TranNominal

TranV2Max

PT Sec

TranV1Max

Threshold

TranV3Dur

CT Prim

TranV2Dur

PT Prim

TranV3Max

CT Sec

Data Recorder

EN50160
Component Logged

Data Recorder

EN50160
Component Logged

EN50160 Frq/Mg

Power Frequency and

Supply Magnitude

EN50160 Vunbal

Voltage Unbalance

EN50160 Flicker

Flicker

EN50160 Hrm Vlt

Harmonics

(up to 40th)

EN50160 Vlt Dp1

Supply Voltage Dips

EN50160 Ihm Vlt

EN50160 Vlt Dp2

EN50160 MSignal

Mains Signalling

Voltage

EN50160 Vlt Dp3

EN50160 Prm-f/V

Parameter data

These data recorders

are disabled by

default (see below).

EN50160 Vlt Dp4

EN50160 Prm-Flk

EN50160 Vlt Dp5

EN50160 Prm-VDp

EN50160 Intrp

Short/Long

Interruptions

EN50160 Prm-Vlr

EN50160 Ovrvlt1

Temporary

Overvoltages

EN50160 Prm-OV

EN50160 Ovrvlt2

EN50160 PrmHrm1

EN50160 Ovrvlt3

EN50160 PrmHrm2