ION 7500 / ION 7600 User’s Guide

I/O Specifications

Chapter 6 - Hardware Reference

Page 171

N

OTE

Because mechanical relays have limited lifetimes, mechanical KYZ relays are typically not suitable for
energy pulsing applications. For energy pulsing applications, consider using Form A outputs in KYZ
mode.

A typical connection and operational details are illustrated below..

N

OTE

The mechanical relays should be protected by external fuses.

Solid-State Relay Outputs

Specifications for the four digital relay (Form A) outputs (D1 through D4) are as
follows:

1

Digital output D4 is configured at the factory to emit pulses for calibration testing purposes.

Operational Block Diagram

STATE

RX1 – RX2

RX2 – RX3

Inactive

Open

Closed

Active

Closed

Open

Pulse

Closed for

duration of pulse

Open for duration

of pulse

R

X1

R

X2

R

X3

N/O

N/C

R

11

R

12

R

13

R

21

R

22

R

23

R

31

R

32

R

33

Specification

Value

Signal Type

Continuous or pulse

1

Maximum Load Voltage

30V

Maximum Load Current

80 mA

Isolation

5,000 Vrms

Scan Time

½ cycle

Connection Type

Captured-wire

Wire Type

AWG 28 to AWG 16

Rear View of Meter

Standard I/O

Solid-State relays