Chapter 5 - Features and Applications

Event Logging

Events produced by a meter’s various ION modules are prioritized and grouped
to facilitate custom logging. Each event is assigned a priority group number based
on its type and severity.

ION Event Priority Groups

Some event groups are preset with a Priority Number as shown in the table below.
You can also define your own priority number for some modules. Priority
numbers from 128-191 appear in the global even log viewer in ION Enterprise
software. Priority numbers from 192-255 are logged, initiate a beep and cause the
window to flash. You can customize these responses to display messages or
perform netsend messages, for example.

The Event Log Controller module allows you to set a priority cutoff for event
logging. Any events with a priority number greater than the cutoff value are
logged, and events with lower priorities are discarded. Refer to the individual
module descriptions and the Event Log Controller module description in the
online ION Programmer’s Reference for more details.

Event Group

Description

Priority Number

Reset

Module reset or re synchronized

5

Setup Change

Module setup changes (setup register changes, label changes, input handle changes)

10

Input Register Change

Inputs of certain modules change value (ie, input to And/Or module changes)

15

I/O State Change

I/O state changes (ie, relay closes)

20

Information

Module produces important user information

25

Warning

Module produces a warning

30

EN50160 Event

(ION 7600 only)

An EN50160 Counter (N

1

or N

2

) increases

50

Failure

A failure has occurred

255

Setpoint

Setpoint condition goes Active or Inactive (ie, Sag/Swell module detects a disturbance)

programmable via