Changing the frequency of logging, Default logging configuration – Multi-Tech Systems 7500 User Manual

Page 54

Advertising
background image

Data Logging Setup

ION 7500 / ION 7600 User’s Guide

Page 54

Chapter 3 - Default Meter Functionality

Changing the Frequency of Logging

The five Periodic Timer modules that control the frequency of different data
recording are as follows:

"Revenue Log Trg" controls the frequency of the logging of revenue values

"Loss Log Trg" controls the frequency of Loss Compensation Data logging

"EgyDmd Log Trg" controls the frequency of logging for the Energy and
Demand Log (this log is used for generating reports using Reporter)

"Hist Log Trg" controls the frequency of Historic Data logging

"Harm Log Trg" controls the frequency of Harmonics logging

N

OTE

The life of the flash memory is estimated at 40 to 50 years of read/writes under normal conditions. If the
meter is programmed to write the data recorders in very short intervals, the life of the flash memory will
be significantly reduced.

Change the value in the Period setup register to change the frequency of data
logging (Period values are specified in seconds). Do not change the Sync Mode
setup register.

For more information about the EN50160 data recorders, refer to “EN50160
Compliance Logging (ION 7600 only)” on page 57
as well as the technical note
Power Quality: ION Meters and EN50160 in Appendix A.

Default Logging Configuration

The following sections describe each Data Recorder and the parameters they log.

Revenue Log

The Revenue Log (Data Recorder #1) is configured for use with UTS MV-90 billing
software. The default values logged by the Revenue Log are as follows:

Parameter

Description

kWh del int

Interval kWh delivered

kWh rec int

Interval kWh received

kVARh del int

Interval kVARh delivered

kVARh rec int

Interval kVARh received

Advertising