Configuring the MeterM@il Feature to Send Alerts

MeterM@il Internal Email Server Feature Technical Note

Page 243

Configuring the MeterM@il Feature to Send Alerts

The Alert module can be configured to send an email alert message to your
workstation – this keeps you informed about certain alarm conditions so you can
act on them.

The Alert module sends an alert whenever its Trigger input is pulsed. You can
connect this input to any module that produces a pulse output. You can use
modules that monitor alarm conditions such as changes in relay status and power
quality problems (surges, sags, swells, outages).

In the example framework above, a Sliding Window Demand module’s output is
monitored so that an alert is sent when the predicted demand value goes above a
certain limit. A Setpoint module is required to determine when the high limit
condition is met, and to send a pulse to trigger the Alert module. When the pulse
is received, the message is sent according to the Alert module’s setup register
values. The example above shows the setup registers that must be configured in
the Alert module for email alerts (see step 4 below for additional setup register
configuration).

N

OTE

The SMTP Server address must be configured correctly before the MeterM@il feature can operate. In
addition, the SMTP Connection Timeout period may need to be extended (e.g. if the SMTP mail server
does not reside on the Ethernet network).

Setting up the meter to send alerts:

1.

Create an Alert module.

2.

Create an ION module that produces a pulse on one of its output registers when
the exceptional event occurs (in the example above, a Setpoint module pulses its
Trigger output when the setpoint condition is reached).

3.

Link the Alert module’s Trigger input register to a pulse output register on the
module created in step 2.

4.

Configure the following Alert module setup registers as follows:

Message – this string register contains the text of the alert to be emailed. You
can use up to 120 alphanumeric characters in your message string. Values
and names from registers linked to the module’s Source inputs can be
included in the message by referencing them in the message string.

Sliding Window

Demand Module

From Power

Meter module

Source

PredDemand

Setpoint Module

Source

Trigger

Alert Module

Trigger

Sending

Event

Lockout

Pending

Destination =

your_email@your_domain.com

Type = Email

Com Port = Ethernet