Alerting via an Alphanumeric Pager

Chapter 5 - Features and Applications

Page 155

Alerting via an Alphanumeric Pager

N

OTE

For detailed information about building a framework for alerting via an alphanumeric pager, refer to the
Alert module description in the online

ION Programmer’s Reference.

If an alphanumeric pager is specified as the destination address in the Alert
module, then an alphanumeric paging service receives a message from the ION
meter.

Once the modem at the paging service is contacted, the ION meter transmits the
following information:

Pager identification number

Local time (year, month, date, hours, minutes, seconds)

Remote site identification

Priority of the alarm

Alert message, with text strings and realtime measured values

To include a module’s Source input in the message, reference the message string by
using the form %Vn, where n is the Source input number. In the following Message
register setting, the kWtot value is %V1. The string includes Source input 1 which
would be the kWtot register from the Power Meter module.

The destination register contains your modem access number for the paging
service provider and is what is dialed out first. The Pager Num register is the pager
access number that is provided by your paging company.