Pasting the Modbus Master Framework into the Meter

Sub-Metering with a Modbus Master Technical Note

Page 327

Pasting the Modbus Master Framework into the Meter

This section describes how to paste the Modbus Master framework into the meter.

C

AUTION

The Modbus Master framework is designed to work with meters that use their factory default framework.
If you paste the Modbus Master framework into a meter that is not using its default configuration, the
custom configuration on your meter can be destroyed.

1.

Ensure that the Modbus Master framework (Modbus_Master.fwn) is located
in your frameworks directory (C:\ION Enterprise\config\fmwk\nd).

2.

Connect to your Modbus Master device in Designer.

3.

Open the Options menu and verify that the Show Toolbox menu item is
checked.

4.

Double-click on the Frameworks folder to access the Advanced Configuration
folder.

N

OTE

Before you paste in the new framework, click on an empty area of the screen. This ensures that no
modules are selected.

5.

Click on the Edit menu and select Paste From Framework.

6.

Select the Modbus Master framework and click Open.

7.

In the Paste Summary dialog box, click OK. This will “free paste” the Modbus
Master framework into the meter. When the pasting is completed, a new folder
called Modbus Master Framework appears.

N

OTE

Refer to the section, “Multiple Modbus Master Devices” if you plan to use this framework in several
Modbus Master devices.

8.

Once you have returned to the main window in Designer, click Send and Save
to save your changes.