Meterm@il technology in a modbus network – Multi-Tech Systems 7500 User Manual

Page 247

Advertising
background image

ION 7500 / ION 7600 User’s Guide

Configuring the MeterM@il Feature to Send Data Logs

MeterM@il Internal Email Server Feature Technical Note

Page 247

MeterM@il Technology in a Modbus Network

The following example illustrates just one of the many uses for the Log Export
module. This Modbus network includes the ION 7500 as the Modbus Master and
the ION 6200 and ION 7300 meters as Modbus slave devices. Configuration is
performed on the framework where the Modbus Master is located for systems that
utilize MeterM@il technology.

Notice that the Modbus Import module supplies values to the Data Recorder
module’s Source inputs. The Modbus Import module’s Slave Addr (slave address)
is set to 113, indicating that the values come from the ION 7300. The Periodic Timer
module’s Period register is set to 900, so the Data Recorder module is pulsed every
fifteen minutes (900 seconds). When it is pulsed the Data Recorder module records
the values in its Source 1-3 inputs. Once the values are successfully recorded, the
Data Recorder module's Record Complete output pulses the Log Export module’s
Send input. The Log Export module then sends all its Source data records that have
not previously been sent to the email specified in the Destination setup register
([email protected]).

Ethernet

RS-485

Unit ID: 113
Location: Office

IP Address: 192.168.1.5

Modbus Master Device

Modbus Slave Devices

Unit ID: 112
Location: Factory

SMTP Server

IP Address: 192.168.1.5

(Modbus Network)

XML Attachment with data
from the ION 7300 meter

Factory Module

Device Namespace = Miami.CompanyX
Device Name = MainMeter

Trigger

Periodic Timer

Module

Period = 900

Modbus Import

Module

Slave Addr = 113

Value 1

Value 2

Value 3

Data Recorder

Module

Source 1

Record

Record Complete

Data Log

Destination = mailto:[email protected]
Gatewayed Device Name = Office
Gatewayed Device Namespace = Default
Gatewayed Device Type = ION 7300

Log Export

Module

Source

Send

Source 2
Source 3

<Data...>

<Device...>

<Recorder id="Data Rec 39"
label="RE39 Data Log">

<Channels>

<Channel id="c1"
label="Vll avg" />
<Channel id="c2"
label="I avg" />
<Channel id="c3"
label="PF sign tot" />

</Channels>

</Recorder>

</Device>

</Data>