Calibration menu and the kctstp/kctrd commands, Calibration menu and help – Multi-Tech Systems 7500 User Manual

Page 188

Advertising
background image

Calibration Menu and the KCTSTP/KCTRD Commands

ION 7500 / ION 7600 User’s Guide

Page 188

Current Probe Inputs Basic Setup Technical Note

Calibration Menu and the KCTSTP/KCTRD Commands

The Calibration menu lets you access setup registers in the meter Factory module.
With the read/write commands KCTRD and KCTSTP, you can program the meter
with parameters appropriate for your current probes.

Calibration Menu and Help

The Calibration menu contains the following calibration commands:

Description of KCTSTP and KCTRD Calibration Commands

The command KCTSTP writes all current probe setup registers. The command
KCTRD reads all current probe setup registers.

KCTSTP <tag> <I> <V> <phase angle> <u> <ch>

Write the external current probe setup registers

Description:
This command writes to non-volatile registers containing the external current
probe parameters

Arguments:
<tag> the current probe model or name tag, maximum of 15 characters; do not
leave spaces
between characters

<I> the RMS value of the nominal primary current of the current probe

<V> the nominal RMS value of the secondary nominal voltage of the current probe

<phase angle> current probe’s phase angle in degrees for constant phase
compensation

<u> selected register group: 1-User Defined 1, 2-User Defined 2

<ch> selected current channel(s): 4-6 (4=I1;5=I2;6=I3), 44 (44 = ALL PHASE
CURRENT CHANNELS: I1,I2,I3)

TERMINAL COMMANDS

KRD

Read All RMS Calibration Constants

KFRD

Read All Force Levels

KFSRD

Read All Full Scale Values

KCTSTP <tag> <I> <V> <phase angle> <u> <ch>

Write Setup for External CT

KCTRD

Read Setup of External CTs

KD

Read Power Meter Module Diagnostics

Advertising
This manual is related to the following products: