Using WebMeter in a Modbus Network

ION 7500 / ION 7600 User’s Guide

Page 280

WebMeter Internal Web Server Feature Technical Note

Factory Module

The Factory module has been configured so that the setup register Device
Namespace
value is “Miami.CompanyX” and the setup register Device Name value
is “MainMeter”.

Modbus Import Module

Three values (Value 1, 2 and 3) are imported from the ION 6200 meter via the
Modbus Import module. These values are then linked to the Web Page module for
the web page to display. The Slave Addr setup register’s value is “113” which
corresponds to the Unit ID of the Slave meter.

Web Page Module

The Web Page module has Values 1, 2 and 3 for its sources. Setup register
Gatewayed Device Namespace has a default value which means the register inherits
the value from the Factory module’s Device Namespace setup register. In this
example, the value is “Miami.CompanyX”.

Setup register Gatewayed Device Name value is “Office”. This value is important if
more than one gatewayed device is sending XML data to the Web Page module.
Otherwise, it can be left as default in which case the register inherits the value from
the Factory module’s Device Name setup register. In this example, the value would
be “MainMeter”.

The value of the Page Location setup register is “Office”. Since the ION 7500 meter’s
IP Address is 192.168.1.5, the web page for the ION 6200 meter will be found at:
http://192.168.1.5/Office.html (or.xml)