External Modem Connections

RS-485 Connections

RS-485 connections are made via the captured-wire connectors on the rear of the meter.
Devices can be connected in series using RS-485 (see diagram to the left). Be sure not to
ground the wires at both ends.

Specifications are as follows:

Connections

1

The lengths of all (+ and –) cable segments must be counted including those that connect devices to
terminal blocks.

Terminal connections on the meter are marked as follows:

Specification

Description

Cable Type

Standard straight-through RS-232 cable

Cable Ends

DB9 female end for mating with the DB9 male connector on the meter

Max. Cable Length

50 feet (15.2 m)

Specification

Value

Baud Rates

300 to 57,600 bps (default is 9,600 bps)

Duplex

Half

Supported Protocols

ION, Modbus RTU, DNP 3.0, FACTORY, Iec870-102, GPS: Arbiter,

GPS: TRUE TIME DATUM, EtherGate, ModemGate (default is ION)

Isolation

Optical isolation from all other inputs and outputs (the COM1 RS-485 port

is not isolated from the COM1 RS-232 port); isolation voltage is 750 V

peak for 10 seconds @ 60 Hz.

Specification

Description

Cable Type

Good quality shielded twisted pair cable, AWG 22 or larger.

Max. Cable Length

4,000 ft. (1219 m)

1

Max. number of

devices per bus

32

Marking

Terminal Function

SHLD

RS-485 Shield

RS-485 Data Minus

+

RS-485 Data Plus

SH + -

SH

COM

RS-485

+

-