ION 7500 / ION 7600 User’s Guide

Display Setup

Chapter 3 - Default Meter Functionality

Page 63

Display Setup

The meter’s front panel display is controlled by three types of ION modules: the
Display Options module, the Scroll module, and Display modules.

Display Options Module Settings
The Display Options module contains setup registers that hold data display
settings such as contrast level, backlight timeout, daylight savings time, and
update time. Settings in the Display Options modules are global, and affect the
entire set of front panel display screens.

Scroll Module Settings

The Scroll module determines the sequence and rate of scrolling for multiple front
panel display screens.

The Trigger outputs of Scroll module are linked to the inputs of Display modules.
When a pulse is sent from the Trigger output of a Scroll module to a linked Display
module, the Display module shows its information on the front panel.

Display Module Settings

Display modules determine the form and content of each display screen

.

Setup Register

Function

Default

Contrast

Sets the global contrast setting for the meter display.

7

Backlight Timeout

Sets the time that the front panel’s backlight stays on after the last press of a front

panel button (in seconds).

300

Display Update Time

Sets the period between data display refreshes (in seconds).

1

Digital Grouping

Sets the numbering format by determining how groups of three digits are

separated.

1,000

Demand Lockout Timeout

Sets the minimum time allowed between consecutive demand resets.

2,160,000

Setup Register

Function

Default

Scroll Delay

Sets the time that will elapse between successive pulses on the

Trigger

outputs when the

scroll module is enabled.

6

Wraparound

Designates the last

Trigger

output (

Trigger

n) before returning to the first

Trigger

in

he order.

10

Freeze Time

Sets the time (in seconds) that the Scroll module remains "frozen" when pulsed from the

Freeze

,

Up

, or

Down

inputs.

120

Setup Register

Function

Default

Screen Type

This specifies the way the linked parameters are displayed on the front panel

screen.

Defaults vary among display

screens. Refer to the

ION

Device Templates

at

www.pwrm.com.

Softkey Number

This assigns a softkey number to the display screen.

Softkey Name

This assigns a softkey name to the display screen.

Screen Title

This assigns a title to the display screen.

Advertising