ION 7500 / ION 7600 User’s Guide

Using the DNP 3.00 Protocol

Chapter 3 - Default Meter Functionality

Page 83

DNP Slave Export Module Settings

The factory-configured DNP Slave Export modules are configured as shown in the
following table.

As the table indicates, some of the setup register settings vary for different
modules. Specifically, BasePoint differs for each module within a group (Analog
Input and Binary Counter are groups), and StaticObj is set to Analog Input for the
11 analog input points and Binary Counter for the three binary counter points.
(StaticObj defines the type of DNP object the module provides when the Master
polls it.)

In addition, Scaling is

OFF

for all but two modules. The only modules that apply

scaling are the Analog Input points that provide Voltage and Current Unbalance
data (labeled Unbalx10) and Frequency data (Labeled Freqx10). These modules
apply x10 scaling.

Setup Register

Setting

BasePoint

Varies – each analog input or binary counter has a different BasePoint

StaticObj

11 modules are

Analog Input

; three are

Binary Counter

EventObj

Disable Event Objects

Deadband

0

FrozStaObj

Disable Frozen Static Objects

FrozEvtObj

Disable Frozen Event Objects

EventClass

Class 1

Scaling

OFF (excluding

Unbalx10

and

Freqx10

which are ON)

IONZero

0

IONFull

0 (1000 for

Unbalx10

and 100 for

Freqx10

)

DNPZero

0

DNPFull

0 (10000 for

Unbalx10

and 1000 for

Freqx10

)