ION 7500 / ION 7600 User’s Guide

Harmonic Voltage

Power Quality: ION Meters and EN50160 Technical Note

Page 317

Harmonics Default Measurements

Register Label

Source Module

Description

V1-Hrm N*

Harmonics

Evaluation

number of valid intervals (voltage on phase 1 within +/- 15% of nominal)

V1-Hrm N invld*

number of invalid intervals

V1-Hrm N1*

number of intervals in which one or more individual harmonics on phase 1 exceed their limits

V1-Hrm N2*

number of intervals in which the THD value on phase 1 exceeds the limit

V2-Hrm N*

number of valid intervals (voltage on phase 2 within +/- 15% of nominal)

V2-Hrm N invld*

number of invalid intervals

V2-Hrm N1*

number of intervals in which one or more individual harmonics on phase 2 exceed their limits

V2-Hrm N2*

number of intervals in which the THD value on phase 2 exceeds the limit

V3-Hrm N*

number of valid intervals (voltage on phase 3 within +/- 15% of nominal)

V3-Hrm N invld*

number of invalid intervals

V3-Hrm N1*

number of intervals in which one or more individual harmonics on phase 3 exceed their limits

V3-Hrm N2*

number of intervals in which the THD value on phase 3 exceeds the limit

PO V1-Hrm N

Store

V1-Hrm N of the previous Observation Period

PO V1-Hrm N1

V1-Hrm N1 of the previous Observation Period

PO V1-Hrm N2

V1-Hrm N2 of the previous Observation Period

PO V2-Hrm N

V2-Hrm N of the previous Observation Period

PO V2-Hrm N1

V2-Hrm N1 of the previous Observation Period

PO V2-Hrm N2

V2-Hrm N2 of the previous Observation Period

PO V3-Hrm N

V3-Hrm N of the previous Observation Period

PO V3-Hrm N1

V3-Hrm N1 of the previous Observation Period

PO V3-Hrm N2

V3-Hrm N2 of the previous Observation Period

V1 THD mean

Sliding Window

Demand

average THD on phase 1 over 10 minutes (used for display purposes)

V2 THD mean

average THD on phase 2 over 10 minutes (used for display purposes)

V3 THD mean

average THD on phase 3 over 10 minutes (used for display purposes)

V1 THD mean mn

Minimum

minimum average THD on phase 1 over 1 week (used for display purposes)

V2 THD mean mn

minimum average THD on phase 2 over 1 week (used for display purposes)

V3 THD mean mn

minimum average THD on phase 3 over 1 week (used for display purposes)

V1 THD mean mx

Maximum

maximum average THD on phase 1 over 10 minutes (used for display purposes)

V2 THD mean mx

maximum average THD on phase 2 over 1 week (used for display purposes)

V3 THD mean mx

maximum average THD on phase 3 over 1 week (used for display purposes)