ION 7500 / ION 7600 User’s Guide

Expansion Boards for Meters with Modbus Master Capability

Digital and Analog I/O Technical Note

Page 215

Power Requirements

The Modbus controller requires 1 Amp at 5Vdc. The I/O modules require between
10-150mA depending on module type.

The 5-Amp power supply can support the Modbus controller (1 Amp) plus two
full racks of digital I/O that fit on a DIN rail rack.

Communications Considerations

The OpenDAC controller provides four wire RS-485 with the Modbus RTU
protocol. To get two additional RS-485, connect a jumper wire between the two
negative and positive terminals.

The Unit ID is set with two dial switches. One switch sets the low word of the ID
(0x0 to 0xF) and the other sets the high word. Protocol and baud rate are set with
the third dial switch, common settings are as follows:

N

OTE

Detailed setup information for the Grayhill OpenDAC system is available at www.grayhill.com and in
Bulletin #812, OpenDAC Modbus Configuration, Installation and Troubleshooting manual. Part
numbers are available on the Power Measurement order form.

Description

Maximum draw per channel for I/O

Controller

1A

Rack

40mA

Digital Inputs

20mA

Digital Outputs

20mA

Analog Voltage Input

75mA

Analog Current Input

75mA

Analog Voltage/Current Outputs

200mA

Thermocouple Modules

75mA

Switch Setting

Parameters

0

9600 baud Modbus RTU

1

19 200 baud Modbus RTU

Remaining settings are for higher baud rates or ASCII protocol