Communications Setup

ION 7500 / ION 7600 User’s Guide

Page 52

Chapter 3 - Default Meter Functionality

1

The factory set Unit ID for COM1 is based on the serial number of the meter, using the last four
numbers before the dash. For example, if the serial number is PA-0009B263-01, the Unit ID is set in
the factory to 9263. After a factory reset, the unit ID number will default to 100.

2

If you have the internal modem order option, the modem shares COM3 with the IRDA optical port.
The modem is factory configured to answer in the number of rings specified by Answer HR Rings (the
Non-Answer HR Rings value is ignored by default). The modem initialization string (

Modem Init

) can

only be altered via software communications.

Refer to the online ION Programmer’s Reference for complete details about all the
setup registers in the Communications module.

Modem Initialization String

The setup register labeled ModemInit is available for ION 7500 and ION 7600
meters with internal modems, and defines the initialization string for the internal
modem (by default, the modem is factory configured to answer on one ring). You
should not require changes to the ModemInit string for normal operation. If you
require advanced modem functionality, you can customize the ModemInit register
with a string up to 47 characters long.

Refer to the Modem AT Commands technical note for information regarding your
internal modem, including details on customizing the modem’s registers.

N

OTE

The ModemInit string is automatically sent to the internal modem when the

ModemInit

setup register is

changed, when the meter is powered up, and when the baud rate of the modem’s Communications
module is changed.

Communications Protocols

By default, all COM ports are configured to use the ION protocol. If you want to
make use of Modbus RTU, DNP, or GPS system, you need to configure the Protocol
setup register for the Communications module that controls the port you want to
use. However, the F

ACTORY

protocol is reserved for the use by Technical Service

Engineers.

Ethernet port

IP Boot Option

A BootP server automatically sets the IP Address, Subnet

Mask, Gateway, and SMTP Mail Server IP Address.

– see your Network Administrator to determine if BootP is

used

BootP

IP Address

This sets the IP Address of the meter

None (if BootP server is

not used)

Subnet Mask

This sets the Subnet Mask setting for the Ethernet Port

None (if BootP server is

not used)

Gateway

This sets the Ethernet Gateway setting for the Ethernet Port

None (if BootP server is

not used)

SMTP Server

This sets the IP Address for the SMTP Mail Server that is

configured to forward mail from the meter to the final

destination

None (if BootP server is

not used)

Communications Port

Setup Register

Function

Default