Mains Signaling Voltage

ION 7500 / ION 7600 User’s Guide

Page 322

Power Quality: ION Meters and EN50160 Technical Note

Mains Signaling Evaluation Module Settings

To enable EN50160 mains signal voltage monitoring, you must specify the signal
frequency of interest and the allowable signal voltage threshold for each of the
three voltage phases. These parameters are held in the Frequency and Limit setup
registers of their respective Mains Signaling Evaluation modules.

The allowable Frequency range is 5 Hz to 2500 Hz (default is 1060 Hz). If this
register is set to 0Hz, then no evaluation will be performed. The voltage threshold
defined by the Limit setup register must be expressed as a percentage of the
fundamental (default is 100%). Refer to the online ION Programmer’s Reference for
more details about this module.

Mains Signaling Default Measurements

* This data is recorded weekly by Data Recorder 31.

Register Label

Source Module

Description

V1-MSignal N*

Mains Signalling

Evaluation

number of valid intervals (voltage on phase 1 within +/- 15% of nominal)

V1-MSignl N ivd*

number of invalid intervals

V1-MSignal N1*

number of valid intervals in which the signaling voltage on phase 1 exceeds a user defined limit

V2-MSignal N*

number of valid intervals (voltage on phase 2 within +/- 15% of nominal)

V2-MSignl N ivd*

number of invalid intervals

V2-MSignal N1*

number of valid intervals in which the signaling voltage on phase 2 exceeds a user defined limit

V3-MSignal N*

number of valid intervals (voltage on phase 3 within +/- 15% of nominal)

V3-MSignl N ivd*

number of invalid intervals

V3-MSignal N1*

number of valid intervals in which the signaling voltage on phase 3 exceeds a user defined limit

PO V1-MSignal N

Store

PO V1-MSignal N of the previous Observation Period

PO V1-MSgnal N1

PO V1-MSgnal N1 of the previous Observation Period

PO V2-MSignal N

PO V2-MSignal N of the previous Observation Period

PO V2-MSgnal N1

PO V2 MSgnal N1 of the previous Observation Period

PO V3-MSignal N

PO V3-MSignal N of the previous Observation Period

PO V3-MSgnal N1

PO V3-MSgnal N1 of the previous Observation Period

V1-MSig N1/N

Arithmetic

N1/N ratio

V2-MSig N1/N

N1/N ratio

V3-MSig N1/N

N1/N ratio

PO V1-MSig N1/N

N1/N ratio of previous Observation Period

PO V2-MSig N1/N

N1/N ratio of previous Observation Period

PO V3-MSig N1/N

N1/N ratio of previous Observation Period