Multi-Tech Systems 7500 User Manual

Page 55

Advertising
background image

ION 7500 / ION 7600 User’s Guide

Data Logging Setup

Chapter 3 - Default Meter Functionality

Page 55

Historic Data Logging

Three data recorders are used to record “standard” power system quantities, such
as phase current, phase voltage and power factor. These recorders are labeled Hist
Mean Log
, Hist High Log, and Hist Low Log. By default, they log the following ION
output register values:

Loss Log

The Loss Log recorder is configured to record loss values. By default, it logs the
following ION parameters:

Harmonics Logging

Two recorders provide various harmonics logs, including K-factor and Total
Harmonics Distortion (THD). These recorders are labeled Harm Mean Log and
Harm High Log. By default, they log the following ION output register values:

Hist Mean Log

Hist High Log

Hist Low Log

Vll ab mean

I avg mean

Vll ab high

I avg high

Vll ab low

I avg low

Vll bc mean

I 4 mean

Vll bc high

I 4 high

Vll bc low

I 4 low

Vll ca mean

kW tot mean

Vll ca high

kW tot high

Vll ca low

kW tot low

Vll avg mean

kVAR tot mean

Vll avg high

kVAR tot high

Vll avg low

kVAR tot low

V unbal mean

kVA tot mean

V unbal high

kVA tot high

V unbal low

kVA tot low

Ia mean

PF lag mean

Ia high

PF lag high

Ia low

PF lag low

Ib mean

PF lead mean

Ib high

PF lead high

Ib low

PF lead low

Ic mean

Freq mean

Ic high

Freq high

Ic low

Freq low

Parameter

Description

MU Ia^2h int

Phase A interval current squared hours

MU Ib^2h int

Phase B interval current squared hours

MU Ic^2h int

Phase C interval current squared hours

MU Vll ab^2h int

Phase A interval voltage Line-to-Line squared hours

MU Vll bc^2h int

Phase B interval voltage Line-to-Line squared hours

MU Vll ca^2h int

Phase C interval voltage Line-to-Line squared hours

Harm Mean Log

Harm High Log

V1 THD mean

I1 K Fac mean

V1 THD high

I1 K Fac high

V2 THD mean

I2 K Fac mean

V2 THD high

I2 K Fac high

V3 THD mean

I3 K Fac mean

V3 THD high

I3 K Fac high

I1 THD mean

I1 THD high

I2 THD mean

I2 THD high

I3 THD mean

I3 THD high

Advertising