Creating Custom Trend Bar Graphs (ION 7500 / ION 7600 only)

ION 7500 / ION 7600 User’s Guide

Page 200

Custom Front Panel Displays Technical Note

4.

Select V

ALUES

to change the displayed parameter in the selected screen.

When you change the value displayed on a screen, you are presented with a
complete list of the meter’s measurements. Using the lists of modules provided,
select the values you want to have displayed on that display screen.

The number of V

ALUES

you can select is a function of the S

TYLE

setting. You

cannot select more values than the S

TYLE

is set to display.

Creating Custom Trend Bar Graphs

(ION 7500 / ION 7600 only)

Bar Graph displays are configured differently than other numeric parameter
displays. Each bar in the display is associated with three specific Source inputs as
follows:

Typically, the minimum and maximum values for each bar graph come from links
to the outputs of Minimum and Maximum ION modules that are themselves
linked to the real-time parameter shown in the bar graph.

N

OTE

This feature works only if the meter’s Volts Mode is NOT set to Demo. When the meter is in Demo mode,
a default trending log showing Vll ab, Ia, PF and KW will be displayed rather than the actual log that has
been linked to the Display module.

Bar Graph

Input

Function

Attributes

First (top)

Source 1

Real-Time value for Bar Graph #1

Bar graph #1 will not appear if you do not link this input

Source 2

Minimum value for Bar Graph #1

Link to the output of a Minimum module

Source 3

Maximum for Bar Graph #1

Link to the output of a Maximum module

Second

Source 4

Real-Time value for Bar Graph #2

Bar graph #2 will not appear if this input is not linked

Source 5

Minimum for Bar Graph #2

Link to the output of a Minimum module

Source 6

Maximum for Bar Graph #2

Link to the output of a Maximum module

Third

Source 7

Real-Time value for Bar Graph #3

Bar graph #3will not appear if this input is not linked

Source 8

Minimum for Bar Graph #3

Link to the output of a Minimum module

Source 9

Maximum for Bar Graph #3

Link to the output of a Maximum module

Fourth

(bottom)

Source 10

Real-Time value for Bar Graph #4

Bar graph #4 will not appear if this input is not linked

Source 11

Minimum for Bar Graph #4

Link to the output of a Minimum module

Source 12

Maximum for Bar Graph #4

Link to the output of a Maximum module