List of parameters for hart communicator – Yokogawa ADMAG AXF User Manual

Page 100

Advertising
background image

IM 1E10C1-E

11-8

11. PARAMETER LIST

List of Parameters for HART Communicator

PV

–32400 to 32400

R

Displays instantaneous flow rate in engineering unit.

A20

Totl

0 to 999999

0

W

Displays and presets forward direction totalized flow rate.

A30

PV AO

2.40 to 21.6 mA

R

Displays current output.

Span

0.0001 to 30000

1.0000

W

Sets flow span in selected unit.

b03

Status group 1

Error

R

Displays self-diagnostics result.

µ

P fault

“ON” shows error status.

EEPROM fault

“OFF” shows normal status.

A/D fault

See “8.2 Self-diagnostics Functions.”

Signal overflow
Coil open
Vel. span> 10 m/s
Vel. span< 0.3 m/s

Status group 2

P. span> 1000p/s

R

Ditto

P. span> 500p/s
P. span> 25p/s
P. span> 15p/s
P. span> 10p/s
P. span> 5p/s
P. span< .0001p/s
T. span> 1000p/s

Status group 3

T. span< .0001p/s

R

Ditto

Analog lmt error
Empty pipe
Multi range err
Coil short
EEPROM no set
EEPROM default
Dev id not entered

Self test

W

Excecutes self-diagnostics.

Auto zero

W

Executes automatic zero adjustment.

C02

Zero tuning

(00) Inhibit

Enable

W

Inhibits or enables automatic zero adjustment.

C01

(01) Enable

D/A trim

ZERO: 3.2 to 5.6 mA

W

Performs fine adjustments of zero and span of current output.

SPAN: 18.4 to 21.6 mA

Scaled D/A trim

ZERO: 3.2 to 5.6 mA

W

Performs fine adjustments of zero and span of scaled analog

SPAN: 18.4 to 21.6 mA

output.

Loop test

4 mA

4 mA

W

Sets test output value.

H02

20 mA
Other (2.72 to 21.28 mA)
End

Status out

(00) Normal

Normal

W

Selects test status output.

H03

(01) Closed (on)
(02) Open (off)

PV Unit

gal/min

m/s

W

Selects engineering unit of “PV”. Displays “Spcl” in case of

L/min

setting unit except 5 units on the left.

Cum/h
ft/s
m/s
(Spcl)

Name

Data Range, Units

Default

Value

R/W

Description

Indicator

of SE