Yokogawa ADMAG AXF User Manual

Page 94

Advertising
background image

IM 1E10C1-E

11-2

11. PARAMETER LIST

List of Parameters for ADMAG SE Indicator and BRAIN Terminal

Indicator

Name

R/W

Description

Data Range, Units

BRAIN

Terminal

Decimal

Point

Default

Value

A00

DISPLAY

R

A10

A10

FLOW RATE(%)

–10.0 to 110.0%

1

R

A20

A20

FLOW RATE

±

300.0

0 to 4

R

A30

A30

TOTAL

0 to 999999

0

W

A31

A31

REV.TOTAL

0 to 999999

W

A32

A32

DIF.TORAL

–999999 to 999999

R

A60

SELF CHECK

GOOD

R

ERROR

µ

F FAULT

EEPROM FAULT
A/D FAULT
SIGNAL OVERFLOW
COIL OPEN
SPAN VEL.> 10 m/s
SPAN VEL.< 0.3 m/s
P.SPAN > 1000 p/s
P.SPAN > 500 p/s
P.SPAN > 25 p/s
P.SPAN > 15 p/s
P.SPAN > 10 p/s
P.SPAN > 5 p/s
P.SPAN < 0001 p/s
T.SPAN > 1000 p/s
T.SPAN < 0001 p/s
4 - 20 LMT ERROR
EMPTY PIPE
MULTIRANGE ERROR
COIL SHORT
EEPROM NO SET
EEPROM DEFAULT

Major outputs display functions.

Displays instantaneous flow rate in %.

Displays instantaneous flow rate in
egineering unit.

Displays and presets forward direction
totalized flow rate.

Displays and resets reverse direction
totalized flow rate.

Displays differential totalized flow rate
between forward and reverse.
(A32=A30–A31)

Displays self-check result.
See “8.2 Self-diagnostics Functions.”