7. OPERATION VIA HART COMMUNICATOR

7.3.4

Setting Parameters

The three parameters must be set to obtain a correct signal.
Nominal size, flow span and meter factor must be set.

(1) Nominal Size

The nominal size is engraved on the data plate of the combined flow tube.

1. Device setup

4. Detailed setup

1. Sensor

4. Sensor config

1. Size unit

ADMAG SE :
Size unit
mm
mm
in

DEL

DEL

ESC

ENTER

1

2

Select “in” (inch).

Press ENTER (F4).

Press SEND (F2) to set data to the ADMAG SE.

ADMAG SE :
Sensor config
1 Size unit in
2 Line size
3 MF
4 Auto zero
5 Flow dir

HELP

SEND

HOME

ENTER

3

Call up “Size unit” setting display.

ADMAG SE :
Size unit
mm
mm
in

DEL

DEL

ESC

ENTER

4. Sensor config

3. Line size

ADMAG SE :
Line size
10.00 in
10.00

DEL

DEL

ESC

ENTER

1

F4

2

Enter “2” with alphanumeric keys.

Press ENTER (F4).

Press SEND (F2) to set data to the ADMAG SE.
By pressing HOME (F3), the display returns to “Online
Menu.”

ADMAG SE :
Sensor config
1 Size unit in
2 Line size
3 MF
4 Auto zero
5 Flow dir

HELP

SEND

HOME

ENTER

3

(ENTER)

F2

(SEND)

Call up “Line size” setting display.

‘2’

ADMAG SE :
Line Size
10.00
2

DEL

DEL

ESC

ENTER

Example: Set “2 inch”.

1. Size unit

2. Line size

F4

(ENTER)

F2

(SEND)