10. OUTLINE

10. OUTLINE

STANDARD SPECIFICATIONS

Note

•For models with no setting switches, a hand-
held terminal is necessary to set parameters.
•Pulse output, status output and alarm output
use commom terminals, therefore, these
functions are not available at the same time.

Excitation method: Pulsed DC excitation
Output Signal:
Current Output: 4 to 20 mA DC

(Load resistance 600

maximum)

Transistor Contact Output(Open-collector):

Pulse, alarm or status output selected by
parameter setting (Contact rating : 30V
DC(OFF), 200mA*(ON))

* In case of FM-Nonincendive type, 135mA

Communication:

HART or BRAIN
(Superimposed on the 4 to 20mA DC signal)

Conditions of Communication Line:

Load Resistance: (including cable resistance)
HART: 230 to 600

, depending on q’ty of field

devices connected to the loop (multidrop
mode)
BRAIN:250 to 600

Load Capacitance: 0.22

µ

F maximum

Load Inductance: 3.3 mH maximum
Distance from Power Line: 15 cm(0.6 ft) or more

(Parallel wiring should be avoided.)

Input Impedance of Receiver Connected to the
Receiving Resistance: 10k

or larger (at 2.4kHz)

(only for HART)

Maximum Cable Length: 2 km* (6500 ft) (when

polyethylene-insulated PVC-sheathed
control cables (CEV cables) are used)

* In case of FM-Nonincendive type, 1.5km(4875ft)

Instantaneous Flow Rate Display Function:

Flow rate can be displayed either in engineering
units or in percent of span. (for models with
indicator)

Totalizer Display Function:

Totalized volume in engineering units can be
displayed by setting a totalizing factor. (for
models with indicator)

Span Setting Function:

Volumetric flow setting is available by setting
volume unit, time unit, flow rate value and flow
tube size.
Volume Unit: m

3

, l, cm

3

, gallon(US),

barrel(=158.987L)
Velocity Unit: m, ft
Time Unit: sec., min., hour, day
Flow Tube Size: mm, inch

Data Security During Power Failure:

Data storage in EEPROM - no back-up battery
required.

Damping Time Constant:

Settable from 0.5 second to 200 seconds. (63%
response time)

Pulse Output Function:

Scaled pulse can be output by setting a pulse
factor.
Pulse Width: Duty 50% or fixed pulse width (0.5,
1, 20, 33, 50, or 100ms) - user selectable.
Output Rate: 0.0001 to 1000pps (when pulse
output function is selected.)

Status Output Function:

One of the followings is selected by parameter
setting.

• Auto 2 Ranges Status Output :
Indicates the selected range for automatic

dual range function.

• Forward and Reverse Status Output :

Indicates the flow direction for forward and
reverse flow measurement mode.

• Totalization Status Output :

Indicates that the internal totalized value ex-
ceeds the set value.

• Low Limit Alarm :

Indicates that flow rate under the low limit set
value.

Alarm Output Function :

Indicates that an alarm occurs (Normal Close
Fixed).

Self Diagnostics Function:

Converter failure, flow tube failure, erroneous
setting, etc. can be diagnosed and displayed (for
models with indicator).

Touch Control:

Parameter setting operation by infrared switches.
(for models with indicator and setting switches)

Electrical Connection:

ANSI 1/2NPT female, DIN Pg13.5 female,
ISO M20 X 1.5 female, JIS G1/2 female

Terminal Connection: M4 size screw terminal
Case Material: Aluminum alloy
Coating: Polyurethane corrosion-resistant coating

Deep sea moss green (Munsell 0.6GY3.1/2.0)

Protection: IP67, NEMA 4X, JIS C0920 water tight type
Mounting: 2-inch pipe mounting
Grounding: 100

or less

*In case of explosion proof type, the protective grounding
must be connected to a suitable IS grounding system.

STANDARD PERFORMANCE

SE***DJ/EJ+SE14(Up to 300m cable length)
Accuracy :

Size in mm

(inch)

Span in m/s

(ft/s)

Accuracy

15 to 400

(0.5 to 16)

0.3 to 1

(1 to 3)

0.5% of span

1 to 10

(3 to 33)

0.25% of span
(at indications below 50% of
span)

0.5% of rate
(at indications 50% of span or
more)

T01.EPS

Repeatability: 0.1% of flowrate (1mm/s minimum)