IM 1E10C1-E

5-19

5. FUNCTION AND DATA SETTINGS

Example 1: Step Input

1%

10%

Step Signal

Flow rate value
after rate limiting

Flow rate value after
damping

9

18

63.2%

Input: 0 to 10%
Damping time constant: 3 sec.
Dead time: 3 sec.
Rate limit value: 1%

Dead time: 3 sec. (Sampling 80 ms

×

18 times)

1

Shows 1% response cause of excessive signal beyond the rate limit. However, actual
output is under damping that described by a solid line.

2

Shows the flow rate signal (1%) of just after damping calculation ( 1 ) and rate limit
value.

3

This signal is recognized as a flow rate signal since it does not return to within the
rate limit value within the dead time.

4

The output signal follows the damping curve and tracks the step signal.

Example 2: Slurry Noise

Slurry Noise

Flow rate value after rate limiting and damping.

Flow rate value after
rate limiting

Dead time: 1 sec.

+1%

–1%

Input: 0 to 10%
Damping time constant: 1 sec.
Dead time : 1 sec.
Rate limit value: 1%

The left figure shows that the slurry
noise is not a flow rate signal.

The rate limit value can be set in parameter No. “n03”.
Setting Range: 0 to 10%

The dead time can be set in parameter No. “n04”.
Setting Range: 0 to 15 sec.

Displayed

Description

Default: 5(%)

Default: 0(%)

(Rate limit function halt at 0)