IM 1E10C1-E

6-10

6. OPERATION VIA BRAIN TERMINAL

6.5.3

Setting Meter Factor

The meter factor is engraved on the data plate of the combined flow tube.

Example: set “1.1200” as meter factor.

Select “B08:MF” by feeding the page with the arrow key and press
ENTER key to call up the following data setup panel.

Display

Description

Turn the power on and the panel as shown on the left appears after
“Please wait...” is displayed for a few seconds.

Pressing the ENTER key causes the initial data panel to be displayed.

Pressing the F4 key or ENTER key causes the menu panel to be
displayed.

Use the arrow key to select “B:SET” with the arrow key and press
the ENTER key.

Then, the parameter panel is displayed.

--WELCOME--
BRAIN TERMINAL
ID:BT200

CHECK CABLE CONNECTION
AND PRESS THE ENT KEY.

UTIL

FEED

ENTER

PARAM
B01:TAG NO

B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s

DATA

DIAG

ESC

PARAM
01:MODEL
SE14-A00
02:TAG NO.

03:SELF CHECK
GOOD

OK

MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET

ENTER

ENTER

HOME

SET

ADJ

ESC

F4

or

ON/OFF

ENTER

PARAM
B06:SIZE UNIT
inch
B07:NOMINAL SIZE
2.00 inch
B08:MF
1.0000

ESC

Press ENTER key on the parameter panel to display the data setup
panel as shown on the left.
(If the security panel appears, enter the security code.*)

Select “1.1200” using the alphanumeric keys. Default:1.0000

SET
B08:MF
1.0000

0

ESC

DATA

DIAG

“1.1200”

CLR

DEL

* For entry of the security code, see IM1C0A11-01E.