Yokogawa ADMAG AXF User Manual

Page 72

Advertising
background image

IM 1E10C1-E

7-22

7. OPERATION VIA HART COMMUNICATOR

(8) Multidrop Mode

Field devices in multidrop mode refer to the connection of several field devices on a
communication single line. Up to 15 field devices can be connected when set in the
multidrop mode. To activate multidrop communication, the field device address must be
changed to a number from 1 to 15. This change deactivates the 4 to 20 mA output and
turns it 4 mA. Refer to Fig. 7.1.2 for the load resistance.

Setting of Multidrop Mode

1. Device setup

4. Detailed setup

4. Outputs

3. HART output

1. Poll addr

ADMAG SE :
Poll addr
0
0

HELP

DEL

ESC

ENTER

Set the polling address (a number from 1 to 15) and press
ENTER (F4).
Then, press SEND (F2) to send the data.

Call up “Poll addr” display.

HART output

Online Menu

Main Menu

4. Utility

1. Configure Communication

1. Polling

ADMAG SE :
HART output
1 Poll addr 1
2 Num req preams 5
3 Burst mode On
4 Burst option PV

HELP

SAVE

HOME

ENTER

1

2

Return to “Online Menu” with HOME (F3).

Return to “Main Menu” with a “previous” key.

Select “Utility”.

Select “Configure Communication”.

Select “Polling”.

F3

(HOME)

Call up “Auto Poll” display.

ADMAG SE :
Online
1 Device setup
2 PV 20Cum/h
3 PV AO 20mA
4 Span 20Cum/h

HELP

SAVE

HOME

ENTER

F4

(ENTER)

‘1’

F2

(SEND)

3

JLK

4

HART Communicator
1 Offline
2 Online
3 Frequency Device
4 Utility

HELP

SEND

HOME

ENTER

4

HART Communicator
Utility
1 Configure Communic
2 system Information
3 Listen for PC
4 Storage Location
5 Simulation

HELP

SEND

HOME

ENTER

5

HART Communicator
Configure Communicat
1 Polling
2 Contrast
3 Off Time
4 Ignore diagnostics

HELP

SEND

HOME

ENTER

Advertising