5.5.10 Alarm Output at Low Flow Limit (Flow Switch)

• In case flow rate decrease under set level, an status signal is output.

PLS/ALM+, PLS/ALM– terminals are for common use with pulse, alarm and other
status output functions. Therefore, in case this function is used, other functions are not
available to use.

Alarm output at low flow limits can be selected “04” in
parameter No. “b10”.

The Low Limit value can be set in parameter No. “b36
as parcentage for 4 to 20 mA.

Hysteresis width is set in parameter No. “b37”.

When using reversed status (ON/OFF) is required,
it can be set in

“N02 Output Mode”.

Display

Description

Code

00
01
02
03
04
05

Pulse output
Alarm output
Forward / reverse flow measurement
Automatic two range switching
Alarm output at low flow limit
Totalozation switch

Content

Output

Hysteresis

Status

Output

On

Default : 5(%)

low flow
limits
value.

Defalt : 00

Defalt : -10(%)

NOTE