IM 1E10C1-E

7-14

7. OPERATION VIA HART COMMUNICATOR

Hot key

1. Span

ADMAG SE :
Flow units
1 Flow unit Cum
2 Time unit h

DEL

SAVE

HOME

ENTER

1

2

Press Hot key.

Select “Span”.

Enter “20.0” with alphanumeric keys.

Press ENTER (F4).

Press SEND (F2) to set data to the ADMAG SE.

Return to the presious display by pressing

or

.

ADMAG SE :
Span
1 Cum/h
1

HELP

DEL

ESC

ENTER

3

Call up “Span” setting display.

ADMAG SE :
Hot key
1 Span 1 Cum/h
2 Enable write
3 New password

DEL

SAVE

ESC

ENTER

ADMAG SE :
Span
1 Cum/h
20.0

DEL

DEL

ESC

ENTER

4

F4

5

(ENTER)

F2

(SEND)

‘20.0’

ADMAG SE :
Hot key
1 Span 20.0Cum/h
2 Enable write
3 New password

DEL

SEND

ESC

ENTER

When the span is set in engineering units using the ADMAG SE front panel key
switches, consideration should be given to the least significant digit which is to be
displayed for all ranges on the rate indicator of the ADMAG SE (parameter A20
FLOW RATE). For example, if the flow rate value is to be displayed to three decimal
places, set the span as “20.000” as opposed to “20.”

NOTE