3 disagreement of indication with actual flow rate – Yokogawa ADMAG AXF User Manual

Page 89

Advertising
background image

IM 1E10C1-E

9-7

9. MAINTENANCE

9.2.3

Disagreement of Indication with Actual Flow Rate

Examine whether or not a valve
exists immediately before the
flow tube (on the upstream side).

NO

Set the parameters correctly.

NO

Adjust zero when the flow tube is
completely filled with liquid and
the velocity is zero.

a. Remove scales. Especially

clean the electrodes and their
vicinity.

b. Remove scales with a soft

brush or a piece of soft cloth.
Never claw or scratch the
lining.

NO

NO

YES

Examine filling with liquid in the flow tube, bubbles and correct
grounding.

Change the piping or mounting to
fill the flow tube with the liquid.
Vertical mounting is effective.

NO

Provide a defoaming device on the
upstream side of the flow tube.

NO

Complete grounding. (The
resistance must be 100

or less.)

See “3.2.1 Protective Ground”

NO

Completely perform end-
treatment of the signal cable with
PVC tubes or insulation tape so
that the conductors, inner shields,
and outer shield do not contact
each other or with the case.

Recheck the liquid property.

Check whether or not the AM011 cable is used for the signal
cable, if there is contact between any two of the cable conductors
(A, B), inner shield (SA, SB), and outer shield (C), and that they
are securely connected to the terminal board.

NO

YES

a. If a valve located immediately

upstream of the flow tube is
used half opened, the indication
may be affected with flow
turbulency.

b. Move the valve downstream of

the flow tube.

c. If the valve must be located on

the upstream side, allow for a
minimum distance to the flow
tube of 10 times the flow tube
diameter or use the valve fully
open.

Check the operation with the
AM012/SE calibrator, and you
will be able to confirm the error of
the converter or of Flow Tube.

Contact the nearest Yokogawa
office or service center.

YES

YES

YES

YES

YES

YES

START

Are parameters

correctly set?

Is zero adjustment

completed?

Is the flow tube

completely filled with

liquid?

Is the liquid free of

bubbles?

Is grounding complete?

Is the signal

cable completely end-

treated?

Is the liquid

likely to cause deposits?

Is a valve located

immediately upstream of

the meter?

Advertising