IM 1E10C1-E

7-2

7. OPERATION VIA HART COMMUNICATOR

7.1.2

Communication Line Requirements

Specifications for Communication Line:

Load resistance:

230 to 600

(including cable resistance)

When multidrop mode, see Figure 7.1.2.

Minimum cable size:

24 AWG, (0.51 mm diameter)

Cable type:

Single pair shielded or multiple pair with overall shield

Maximum twisted-pair length:

6,500 ft (2,000 m)

Maximum multiple twisted-pair length:

3,200 ft (1,000 m)

Use the following formula to determine cable length for a specific application;

L =

65

×

10

6

(R

×

C)

(C

f

+10,000)

C

where:

L = length in feet or meters
R = resistance in ohms, current sense resistance
C = cable capacitance in pF/ft or pF/m
C

f

= 50,000 pF

800

230

571

500

444

400

363 333

307 285

266

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

600

400

200

0

Load

Resistance

(

)

Q’ty of connected field devices

* Maximum Load Voltage: 600

Ω ×

25 mA = 15 V

Figure 7.1.2 Load Resistance and Quantity of Devices in Multidrop Mode

The above graph shows the load resistance in case that each current output of all
connected transmitters is 4 mA.