9. MAINTENANCE

Releasing from Loop Test:

There are four methods which cause the simulated output to return to a normal flow
reading.

1. Wait 10 minutes to automatically release from the test mode.
2. Turn the power off to the ADMAG SE.
3. Execute “End”. (See the following for this procedure.)
4. Abort “Loop Test”. Press ABORT (F3).

ADMAG SE :
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End

DEL

DEL

ABORT

ENTER

1

2

To finish the loop test, select “End”, and press ENTER (F4).

Press OK (F4).

On “Loop test” display.

ADMAG SE :
NOTE-loop may be
Returned to automatic
control

DEL

DEL

ABORT

OK

F4

(OK)

×

3

F4

(ENTER)

(2) Status Output Test

ADMAG SE has one status output for alarm or other functions. It can be output for test.
After the status output test, return the status output parameter to “Normal”.

1. Device setup

2. Diag/Service

3. Status out

ADMAG SE :
Status out
Normal
Normal
Close (on)
Open (off)

DEL

DEL

ESC

ENTER

1

2

Select “Closed” (example) and press ENTER (F4).

Press SEND (F2).

Call up “Status out” display.

ADMAG SE :
Diag/Service
1 Test device
2 Loop test
3 Status out

DEL

SEND

HOME

ENTER

F2

(SEND)

F4

(ENTER)

When the status output test is executed, the current output is fixed 4 mA.

NOTE