7-20

7. OPERATION VIA HART COMMUNICATOR

ADMAG SE :
Settting fld dev
output to 20mA

HELP

SAVE

ABORT

OK

11

12

Press OK (F4). The output signal of 100% is output.

Voltmeter reading: 5.210

Enter the reading of the voltmeter (5.210), and press ENTER
(F4)
.

Voltmeter reading: 5.000

Select “Yes” and press ENTER (F4).
Returning fld dev to original output” appears.

Press OK (F4).

ADMAG SE :
Scaled output: 5.210
equal readout
device?
1 Yes
2 No

HELP

DEL

ABORT

ENTER

13

ADMAG SE :
Enter meter value
5.000000
5.000000

HELP

DEL

ABORT

ENTER

ADMAG SE :
NOTE-Loop may be
returned to automatic
control

DEL

DEL

ABORT

OK

14

‘5.21’

F4

(ENTER)

F4

(ENTER)

F4

(OK)

F4

(OK)

D/A trim should be executed only at single range mode. If D/A trim is executed at Bi
direction mode, it is feared that the current output becomes 108%.

IMPORTANT