3 setting for test output using hart communicator, Setting for test output using hart communicator -3 – Yokogawa ADMAG AXF User Manual

Page 85

Advertising
background image

IM 1E10C1-E

9-3

9. MAINTENANCE

9.1.3

Setting for Test Output Using HART Communicator

(1) Loop Test

This feature can be used to output a fixed current from 2.72 mA to 21.28 mA for loop
check.

Setting of Loop Test

1. Device setup

2. Diag/Service

2. Loop test

ADMAG SE :
WARN-Loop should be
removed from
automatic control

DEL

DEL

ABORT

OK

1

2

Set the control loop in manual mode, and press OK (F4).

Select “Other”, and press ENTER (F4).

1. 4mA:

Outputs a 4mA current signal

2. 20mA:

Outputs a 20mA current signal

3. Other:

Sets a desired output with the alphanumeric keys

4. End: Exits

Enter “12”, and press ENTER (F4).

Press OK (F4).
A fixed current of 12mA is output.

ADMAG SE :
Output

4.000

HELP

DEL

ABORT

ENTER

3

Call up “Loop test” display.

ADMAG SE :
Choose analog output
level
1 4mA
2 20mA
3 Other
4 End

DEL

DEL

ABORT

ENTER

ADMAG SE :
Fld dev output is
fixed at 12.000 mA

DEL

DEL

ABORT

OK

4

F4

(OK)

‘1 2’

×

2

Example: Set “12mA (50%)” as test output.

2. Loop test

F4

(ENTER)

F4

(OK)

F4

(ENTER)

1. In case “Bi direction” is set at “Output function”, the setting range is available

with –108 to +108%. Please set the loop test value in +/– percentage based on the
larger flow span within forward and reverse flow span.

2. In case “Auto 2 ranges” is set at “output function”, the loop test setting value

should be set in percentage based on the second range.

NOTE