IM 1E10C1-E

6-5

6. OPERATION VIA BRAIN TERMINAL

6.5 Setting Parameters

The three parameters must be set to obtain a correct signal.
Nominal size, flow span and meter factor must be set.

6.5.1

Setting Nominal Size

Example: Nominal Size 2.00 inch

Select “B06:SIZE UNIT” by feeding the page with the arrow key
and press ENTER key to call up the following data setup panel.

Display

Description

Turn the power on and the panel as shown on the left appears after
“Please wait...” is displayed for a few seconds.

Pressing the ENTER key causes the initial data panel to be displayed.

Pressing the F4 key or ENTER key causes the menu panel to be
displayed.

Use the arrow key to select “B:SET” with the arrow key and press
the ENTER key.

Then, the parameter panel is displayed.

--WELCOME--
BRAIN TERMINAL
ID:BT200

CHECK CABLE CONNECTION
AND PRESS THE ENT KEY.

UTIL

FEED

ENTER

PARAM
B01:TAG NO

B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s

DATA

DIAG

ESC

PARAM
01:MODEL
SE14-A00
02:TAG NO.

03:SELF CHECK
GOOD

OK

MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET

ENTER

ENTER

HOME

SET

ADJ

ESC

F4

or

ON/OFF

ENTER

PARAM
B04:FLOW UNIT
m
B05:TIME UNIT
/S
B06:SIZE UNIT
mm

ESC

Press ENTER key on the parameter panel to display the data setup
panel as shown on the left.
(If the security panel appears, enter the security code.*)

Select “inch” using the arrow keys. Default:mm

SET
B06:SIZE UNIT
mm
< mm >
< inch >

ESC

DATA

DIAG

* For entry of the security code, see IM1C0A11-01E.

NOTE