IM 1E10C1-E

7-21

7. OPERATION VIA HART COMMUNICATOR

(7) Burst Mode

The ADMAG SE continuously sends the data stored in it when the burst mode is set
“On”. Either one of instantaneous flow rate, output in %, totalization values and current
output can be selected and sent. The data is sent intermittently as a digital signal when
the ADMAG SE is set in the burst mode.

Setting of Burst Mode

1. Device setup

4. Detailed setup

4. Outputs

3. HART output

4. Burst option

ADMAG SE :
Burst option
********
PV
% range/current
Process vars/crnt

HELP

DEL

ESC

ENTER

Set the data to be sent.

• Instantaneous flow rate (PV)
• Output in % and current output (% range/current)
• Instantaneous flow rate, totalization value* and current

output (Process vars/crnt)
* “Totl”, “Reverse total” or “Diff. total”

Call up “Burst option” display.

3. HART output

3. Burst mode

ADMAG SE :
Burst mode
Off
Off
On

DEL

DEL

ESC

ENTER

1

F4

2

Set “ON” and press ENTER (F4).

Press SEND (F2).

(ENTER)

F2

(SEND)

Call up “Burst mode” display.

ADMAG SE :
HART output
1 Poll addr 0
2 Num req preams 5
3 Burst mode On
4 Burst option PV

HELP

SEND

HOME

ENTER

F4

(ENTER)

F2

(SEND)

Releasing from Burst Mode

Call up “Burst mode” display, and set “Off”.