7 other important points, Other important points -12 – Yokogawa ADMAG AXF User Manual

Page 50

Advertising
background image

IM 1E10C1-E

6-12

6. OPERATION VIA BRAIN TERMINAL

Select “PROVIDED” in “D02:FL USER SEL.
Default:NOT PROVIDED

In “D03:FL USER SPAN” set the value of 100% flow rate to be
displayed in “A20:FLOW RATE” The user-defined unit is set in
D10:FL USER UNIT” Default:100.0


Set the user-defined unit in “D10:FL USER UNIT

The instantaneous flow rate in user-defined unit can be displayed in
A20:FLOW RATE

DIAG

DATA

Display

Description

PARAM
D02:FL USER SEL
PROVIDED
D03:FL USER SPAN
20000.0
D10:FL USER UNIT
kg/h

DATA

DIAG

ESC

PARAM
A10:FLOW RATE(%)
1 0 0 . 0 %
A20:FLOW RATE
2 0 0 0 0 . 0 k g / h
A30:TOTAL

0

ESC

PRNT

(2) User-Defined Unit for Totalization Value

User-defined unit can be added to the totalization display in “A30 TOTAL

Set the user-defined unit in “E10:TL USER UNIT

The totalization value in user-defined unit can be displayed in
A30:TOTAL

DIAG

DATA

Display

Description

PARAM
E04:TOTAL SET
INHIBIT
E05:TL SET VALUE
0
E10:TL USER UNIT
kg

DATA

DIAG

ESC

PARAM
A10:FLOW RATE(%)
1 0 0 . 0 %
A20:FLOW RATE
2 0 0 0 0 . 0 k g / h
A30:TOTAL

4 0 0 0 0 k g

ESC

6.7 Other Important Points

(1) The automatic power-off function turns the BT200 off automatically with no key

access for about 5 minutes or more. However, this function does not operate when
the BT200 is displaying “A10:FLOW RATE (%)” or “A20:FLOW RATE”

(2) When “A10:FLOW RATE (%)” or “A20:FLOW RATE” is displayed, the data are

updated every 5 seconds.

(3) UPLOAD/DOWNLOAD functions which can copy the setting date between

ADMAG SE and BT200 are provided. (For details, see the “BT200 Instruction
Manual IM 1C0A11-01E.”)
Parameters that can be copied are as follows:
B02 DAMPING, B03 FLOW SPAN, B04 FLOW UNIT, B05 TIME UNIT,
B06 SIZE UNIT, B07 NOMINAL SIZE, B10 OUTPUT FUNC, B11 4-20 ALM OUT,
D01 DISP SELECT, D02 FL USER SEL, D03 FL USER SPAN,
D10 FL USER UNIT, E01 TOTAL UNIT, E02 TOTAL SCALE,
E03 TOTAL LOWCUT, E04 TOTAL SET, E05 TL SET VALUE,
E10 TL USER UNIT, F01 PULSE UNIT, F02 PULSE SCALE,
F03 PULSE LOWCUT, F04 PULSE WIDTH, G01 4-20 LOW CUT,
G02 4-20 LOW LMT, G03 4-20 H LMT