3 csa, Csa -3 – Yokogawa ADMAG AXF User Manual

Page 106

Advertising
background image

IM 1E10C1-E

12-3

12. EXPLOSION PROTECTED TYPE INSTRUMENT

(2) Wiring (Following contents refers "DOC.

No. NFM008-A13 P.1 and P.2")

Hazardous(Classified)
Location
Class I, Division 2
Groups A, B, C, D

Hazardous(Classified)
Location
Class I, Division 2
Groups A, B, C, D

Associated
Apparatus

Nonhazardous
Location

Model SE14 Magnetic
Flow Converter

Control
Equipment
(Note 1)

(Note 3)
(Note 4)
(Note 5)

Nonincendive Field Wiring Parameters:

Output signal

Analog output

Signal name

Current Output

Voc

(V)

19.7

Isc

(mA)

21.6

Ca

(

µ

F)

0.3

La

(mH)

10

The nonincendive field wiring concept allows
interconnection of two FM Approved Nonincendive
Apparatuses with nonindendive field wiring parameters
not specifically examined in combination as a system
when:
Voc

Ϲ

Vmax, Isc

Ϲ

Imax, Ca

м

Ci+C cable, La

м

Li+L cable

Input signal

Contact output

Signal name

Transistor Output

Vmax

(V)

30

Imax

(mA)

135

Ci

(

µ

F)

0.1

Li

(mH)

0

The nonincendive field wiring concept allows
interconnection of two FM Approved Nonincendive
Apparatuses with nonindendive field wiring parameters
not specifically examined in combination as a system
when:
Voc or Vt

Ϲ

Vmax, Isc or It

Ϲ

Imax,

Ca

м

Ci+C cable, La

м

Li+L cable

NOTE

1. Control epuipment connected to the Model
SE14 magnetic flow converter must not use or
generate more than 250V rms or V dc.
2. Installation should be in accordance with the
National Electrical Code ANIS/NFPA 70.
3. The configuration of associated Apparatus
must be Factory Mutual Reseach Corporation
Approval under Nonincendive Field Wiring
Concept or be a simple apparatus (a device
which can neither generate nor store more
than 1.2V, 0.1A, 25mW, or 20 micro-J, ex.
Swithces, thermocouples, LED's and RTD's).
4. Associated Apparatus manufacture's
installation drawing must be followed when
installing this equipment.
5. Associated Apparatus connection is
representative of each input and output signal
connection. Each signal shall be wired in a
separate shielded cable.
6. No revision to drawing without prior Factory
Mutual Reseach Corporation Approval.

(3) Operation

WARNING

• DO NOT DISCONNECT WHILE CIRCUIT IS
LIVE UNLESS LOCATION IS KNOWN TO BE
NONHAZARDOUS.
• NI CLI DIV2, GPS ABCD WITH
NONINCENDIVE FIELD WIRING
PARAMETERS TO CLI DIV2, GPS ABCD PER
DWG NFM008-A13 P.1 & P.2. (Refer to (2))
• Do not connect BRAIN TERMINAL or HART
Communication in Hazardous locations.

(4) Maintenance and Repair

WARNING

The instrument modification or parts replacement
by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void the approval of Factory Mutual Reseach
Corporation.

12.3 CSA

(1) Technical Data

Class I, Groups B, C & D; Class II, Groups E, F &

G; Class III; Encl Type 4X

Electrode Circuit : 41V max. 6//6.25Hz

Temperature Code : T6

Ambient Temperature : -20 to +60

°

C

(2) Wiring

WARNING

• All wiring shall comply with Canadian Electrical
Code Part I and Local Electrical Code.
• Note a warning label worded as follows.
Warning : A SEAL SHALL BE INSTALLED

WITHIN 50cm OF THE
ENCLOSURE.

UN SCELLEMENT DOIT ÉTRE

INSTALLÉ À MOINS DE 50cm DU
BOÎTIER.