7 limiting current output, Limiting current output -12 – Yokogawa ADMAG AXF User Manual

Page 31

Advertising
background image

IM 1E10C1-E

5-12

5. FUNCTION AND DATA SETTINGS

5.5.7

Limiting Current Output

(1) 4 to 20mA Low Cut Output (Current output nearby 0% range)

• This function makes it possible to reduce fluctuations in the 0% region to reduce it to

0%.

Display

Description

Default : 00

Output

Set value

Setting range: 0 to 10% Default:0(%)

0.5%

0.5%

4mA

Hysteresis:1% fixed

5.6mA(10%)

(2) 4 to 20mA Low Limit

• This function limits the low end of the analog output.
• The default value is set at –20%, and –10% as reverse flow limit. Please set in case

other setting is required.

• 2.4mA or less output in alarming is also limited.

Display

Description

Default : -20(%)

Output

4mA

Setting Range: –20 to 100%

Default: –20%

5.6mA(10%)

(3) 4 to 20mA High Limit

• This function limits the high end of the analog output.
• The default value is set at 120%, and please set in case other setting is required.
• 21.6mA or more output in alarming is also limited.

Display

Description

Default : 120(%)

Output

18.4mA (90%)

Setting Range: 0 to 120%

Default: 120%

4mA