7. OPERATION VIA HART COMMUNICATOR

ADMAG SE :
Setting fld dev
output to 4mA

HELP

SAVE

ABORT

OK

8

9

ADMAG SE :
Enter meter value
1.000000
1.000000

DEL

DEL

ABORT

ENTER

F4

VWX

2

(ENTER)

10

ADMAG SE :
Scaled output: 1.000
equal readout
device?
1 Yes
2 No

DEL

DEL

ABORT

ENTER

F4

(ENTER)

ADMAG SE :
Trim will be scaled
from 4.000 to 20.000
1 Proceed
2 Change

HELP

SAVE

ABORT

ENTER

3

4

Select “Change”, and press ENTER (F4).
The same operations as for “D/A trim” are required when
selecting “Proceed”.

Enter the read value on the meter when the signal is 4 mA. In
this case, enter the value of the voltage across a 250

resistor

(1 V), and press ENTER (F4).

Enter the read value on the meter when the signal is 20 mA.
Then, enter “5” (5 V), and press ENTER (F4).

Select “Proceed” and press ENTER (F4).

Connect the voltmeter, and press OK (F4).

Press OK (F4). The output signal of 0% is output.

Voltmeter reading: 1.010

Enter the reading of the voltmeter (1.010), and press ENTER
(F4)
.
(The output of the ADMAG SE changes.)

Voltmeter reading: 1.000

Because the reading on the voltmeter is 1.000, select “Yes” and
press ENTER (F4).
If the reading is not 1.000, select “No”.
Repeat step until the voltmeter reads 1.000 V.

ADMAG SE :
Set scale- Hi output
value
20.000000
20.000000

HELP

DEL

ABORT

ENTER

5

ADMAG SE :
Set scale- Lo output
value
4.000000
4.000000

HELP

DEL

ABORT

ENTER

ADMAG SE :
Trim will be scaled
from 1.000 to 5.000
1 Proceed
2 Change

DEL

DEL

ABORT

ENTER

6

7

ADMAG SE :
Connect reference
meter

HELP

DEL

ABORT

OK

‘1’

‘1.01’

F4

(ENTER)

‘5’

F4

(ENTER)

F4

(ENTER)

F4

(OK)

F4

(OK)

9