6. OPERATION VIA BRAIN TERMINAL

6.5.2

Setting Flow Span

Example: Flow span 30.0 m

3

/h

Select “B03:FLOW SPAN” using the arrow key and press ENTER
key to call up the following data setup panel.

Display

Description

Turn the power on and the panel as shown on the left appears after
“Please wait...” is displayed for a few seconds.

Pressing the ENTER key causes the initial data panel to be displayed.

Pressing the F4 key or ENTER key causes the menu panel to be
displayed.

Use the arrow key to select “B:SET” with the arrow key and press
the ENTER key.

Then, the parameter panel is displayed.

--WELCOME--
BRAIN TERMINAL
ID:BT200

CHECK CABLE CONNECTION
AND PRESS THE ENT KEY.

UTIL

FEED

ENTER

PARAM
B01:TAG NO

B02:DAMPING
3.0 s
B03:FLOW SPAN
1.00 m/s

DATA

DIAG

ESC

PARAM
01:MODEL
SE14-A00
02:TAG NO.

03:SELF CHECK
GOOD

OK

MENU
A:DISPLAY
B:SET
C:ADJUST
D:DISP SEL
E:TOTAL SET
F:PULSE SET

ENTER

ENTER

HOME

SET

ADJ

ESC

F4

or

ON/OFF

ENTER

SET
B03:FLOW SPAN
1.0000 m/s
0

DEL

CLR

ESC

“30.0”

Press ENTER key on the parameter panel to display the data setup
panel as shown on the left.
(If the security panel appears, enter the security code.*)

Enter “30.0” using the alphanumeric keys. Default:1.0000(m/s)
(This “B03: FLOW SPAN” is for entering the value, not units.)

* For entry of the security code, see IM1C0A11-01E.