19
Write Your Motion Control Programs Chapter 3
7. On the Instruction Block
Selector window that appears,
type MC_Reset on the default
entry field. Choose MC_Reset
and click OK.
Create and Assign Variables and Values for the Axis_PowerUp Program
1. On the Project Organizer pane,
double-click Global Variables to
bring up the Variables window.
Add the following variables with
these corresponding data types
and initial values.
Your ladder rung should appear as follows.
Variables and Initial Values for Axis_PowerUp Program
Variable Name
Data Type
Initial Value
Simulator
AXIS_REF
PowerUpAxis
BOOL
TRUE
PowerDone
BOOL
SWReset
BOOL
False